Inviscid and Viscous Numerical Models Compared to Experimental Data in a Small Data Center Test Cell

[+] Author and Article Information
Ethan Cruz

International Business Machines,
Austin, TX 78758

Yogendra Joshi

Georgia Institute of Technology,
Atlanta, GA 30332

Contributed by the Electronic and Photonic Packaging Division of ASME for publication in the Journal of Electronic Packaging. Manuscript received October 2, 2012; final manuscript received July 1, 2013; published online July 24, 2013. Assoc. Editor: Saurabh Shrivastava.

J. Electron. Packag 135(3), 030904 (Jul 24, 2013) (6 pages) Paper No: EP-12-1092; doi: 10.1115/1.4024944 History: Received October 02, 2012; Revised July 01, 2013

Both localized power densities and overall power consumption within the data center continue to rise, following the same upward trend as the information technology (IT) equipment stored within the data center. Air cooling this increasing power has proved a significant challenge at both the IT equipment and data center level. In order to combat this challenge, computational fluid dynamics and heat transfer (CFD/HT) models have been employed as the dominant technique for the design and optimization of both new and existing data centers. This study is a continuation of earlier comparisons of CFD/HT models to experimentally measured temperature and flow fields in a small data center test cell. It compares an inviscid model, a laminar flow model, and three turbulence models to six sets of experimentally collected data. The six sets of data are from two different IT equipment rack power dissipations using three different layouts of perforated tiles. Insight into the location of the deviation between the different CFD/HT models and experimental data are discussed, along with the computational effort involved in running the models. A new grid analysis was performed on the different CFD/HT models in order to try to minimize computational effort. The inviscid model was able to run with a smaller grid size than the viscous models and even for the same size grid was found to run 30% faster than the fastest viscous model. Due to both the reduced grid size and computational effort (due to the simpler equation set), the inviscid model ran over thirty times faster than the next fastest model. The fact that the inviscid model ran the fastest is not surprising, however what was not expected is that the inviscid model was also found to have the smallest deviations from the experimental data for all six of the cases. This is most likely due to the arrangement of the data center test cell with the relatively few high velocity air jets and large open space around the IT equipment. More tightly packed data centers with higher air velocities and turbulent mixing conditions will certainly produce different results than those found in this study.

FIGURES IN THIS ARTICLE
<>
Copyright © 2013 by ASME
Your Session has timed out. Please sign back in to continue.

References

American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE), 2012, Datacom Equipment Power Trends and Cooling Applications, 2nd ed., ASHRAE, Atlanta, GA.
Iyengar, M., Schmidt, R. R., Hamann, H., and VanGilder, J., 2007, “Comparison Between Numerical and Experimental Temperature Distributions in a Small Data Center Test Cell,” Proceedings of IPACK’07, Vancouver, Canada, July 8–12, ASME Paper No. IPACK2007-33508. [CrossRef]
Zhang, X., VanGilder, J., Iyengar, M., and Schmidt, R., 2008, “Effect of Rack Modeling Detail on the Numerical Results of a Data Center Test Cell,” Proceedings of the Inter Society Conference on Thermal Phenomena (ITHERM2008), Orlando, FL, May 28–31. [CrossRef]
Cruz, E., Joshi, Y., Iyengar, M., and Schmidt, R., 2009, “Comparison of Numerical Modeling to Experimental Data in a Small Data Center Test Cell,” Proceedings of IPACK’09, San Francisco, CA, July 19–23, ASME Paper No. InterPACK2009-89306. [CrossRef]
Cruz, E., Joshi, Y., Iyengar, M., and Schmidt, R., 2009, “Comparison of Numerical Modeling to Experimental Data in a Small, Low Power Data Center Test Cell,” Proceedings of the International Mechanical Engineering Congress and Exposition (IMECE), Lake Buena Vista, FL, November 13–19, ASME Paper No. IMECE2009-12860. [CrossRef]
Patel, C., Bash, C., and Belady, C., 2001, “Computational Fluid Dynamics Modeling of High Compute Density Data Centers to Assure System Inlet Air Specifications,” Proceedings of IPACK’01, Kauai, HI, July 8–13.
Shrivastava, S., Iyengar, M., Sammakia, B., Schmidt, R., and VanGilder, J., 2006, “Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/ft2,” 10th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronics Systems (ITHERM'06), San Diego, CA, May 30–June 2. [CrossRef]
Rambo, J., and Joshi, Y., 2007, “Modeling of Data Center Airflow and Heat Transfer: State of the Art and Future Trends,” Distrib. Parallel Databases, 21(2–3), pp. 193–225. [CrossRef]
Schmidt, R., Iyengar, M., and Caricari, J., 2007, “Data Center Housing the World's 3rd Fastest Supercomputer—Above Floor Thermal Measurements Compared to CFD Analysis,” Proceedings of IPACK’07, Vancouver, Canada, July 8–12, ASME Paper No. IPACK2007-33899. [CrossRef]
Amemiya, Y., Iyengar, M., Herman, H., O'Boyle, M., Schappert, M., Shen, J., and van Kessel, T., 2007, “Comparison of Experimental Temperature Results With Numerical Modeling Predictions of a Real-World Compact Data Center Facility,” Proceedings of IPACK’07, Vancouver, Canada, July 8–12, ASME Paper No. IPACK2007-33899. [CrossRef]
Hamann, H., Lacey, J., O'Boyle, M., Schmidt, R., and Iyengar, M., 2008, “Rapid Three Dimensional Thermal Characterization of Large Scale Computing Facilities,” IEEE Trans. Compon. Packag. Technol., 31(2), pp. 444–448. [CrossRef]
Toulouse, M., Doljac, G., Carey, V., and Bash, C., 2009, “Exploration of a Potential-Flow-Based Compact Model of Air-Flow Transport in Data Centers,” Proceedings of the International Mechanical Engineering Congress and Exposition (IMECE2009), Lake Buena Vista, FL, November 13–19, ASME Paper No. IMECE2009-10806. [CrossRef]
ansysfluent, 2013, Anysis Inc., Canonsburg, PA, www.ansys.com
IBM IntelliStation, 2013, IBM Corp., Armonk, NY, www.ibm.com

Figures

Grahic Jump Location
Fig. 1

Data center test cell

Grahic Jump Location
Fig. 3

RMS difference versus solution time

Grahic Jump Location
Fig. 4

Absolute temperature difference between the measured data and the various flow models for all nine heights for the 1 tile, 23 kW case

Tables

Errata

Discussions

Some tools below are only available to our subscribers or users with an online account.

Related Content

Customize your page view by dragging and repositioning the boxes below.

Related Journal Articles
Related eBook Content
Topic Collections

Sorry! You do not have access to this content. For assistance or to subscribe, please contact us:

  • TELEPHONE: 1-800-843-2763 (Toll-free in the USA)
  • EMAIL: asmedigitalcollection@asme.org
Sign In